These tables list the minimum uniform energy factors (UEF) required by federal regulations for some of the most common types and sizes of water heaters. 
Note: These values apply to water heaters manufactured before May 6, 2029.

General Information

Consumer Gas-Fired Instantaneous (> 50,000 Btu/h, ≤ 200,000 Btu/h) - Minimum UEF*

Volume (gallons)Max Rating
0 ≤ GPM < 1.7
Max Rating
1.7 ≤ GPM < 2.8
Max Rating
2.8 ≤ GPM < 4.0
Max Rating GPM ≥ 4.0
< 20.800.810.810.81

*Values from Title 20 §1605.1 Table F-2

Consumer Gas-Fired Storage (≤ 75,000 Btu/h) - Minimum UEF*

Volume (gallons)0 ≤ FHR < 1818 ≤ FHR < 5151 ≤ FHR < 75FHR ≥ 75
300.290.540.600.65
400.270.520.580.64
500.250.500.560.63
550.240.490.550.62
600.610.740.770.79
750.600.730.760.78
800.600.730.760.78

*Values from Title 20, §1605.1 Table F-2

Residential-Duty Commercial Gas-Fired Storage (> 75,000 Btu/h, ≤ 105,000 Btu/h) - Minimum UEF†

Volume (gallons)0 ≤ FHR < 1818 ≤ FHR < 5151 ≤ FHR < 75FHR ≥ 75
500.220.480.550.61
600.210.460.530.61
750.200.450.520.59
800.200.440.510.59

†Values from Title 20, §1605.1 Table F-5

Consumer Electric Instantaneous (≤ 12 kW) - Minimum UEF*

Volume (gallons)Max Rating
0 ≤ GPM < 1.7
Max Rating
1.7 ≤ GPM < 2.8
Max Rating
2.8 ≤ GPM < 4.0
Max Rating GPM ≥ 4.0
< 20.910.910.910.92

*Values from Title 20, §1605.1 Table F-2

Residential-Duty Commercial Electric Instantaneous (> 12 kW, ≤ 58.6 kW) - Minimum UEF†

Volume (gallons)Max Rating
0 ≤ GPM < 1.7
Max Rating
1.7 ≤ GPM < 2.8
Max Rating
2.8 ≤ GPM < 4.0
Max Rating GPM ≥ 4.0
< 20.800.800.800.80
Btu/h
British thermal units per hour
kW
Kilowatt
GPM
Gallons per minute
FHR
First hour rating
UEF
Uniform Energy Factor

†Values from Title 20, §1605.1 Table F-5

Consumer Electric Storage - Minimum UEF*

Volume (gallons)0 ≤ FHR < 1818 ≤ FHR < 5151 ≤ FHR < 75FHR ≥ 75
300.860.920.920.93
400.850.910.920.93
500.840.910.920.93
550.840.910.920.93
601.861.982.052.18
751.841.962.032.16
801.841.962.032.15

*Values from Title 20, §1605.1 Table F-2

Tabletop - Minimum UEF*

Volume (gallons)Max Rating
0 ≤ GPM < 1.7
Max Rating
1.7 ≤ GPM < 2.8
Max Rating
2.8 ≤ GPM < 4.0
Max Rating GPM ≥ 4.0
300.460.830.890.94
400.400.790.870.92

*Values from Title 20, §1605.1 Table F-2